Operating Instructions
Chapter 4 - Parameters and Menu Structure
Parameters (M3)
52 | 187
Siemens Industry, Inc.
Siemens BT300 HVAC Drive
DPD01809
Smart Infrastructure
2019-05-29
Structure
Parameter
Unit
Min
Max
Default
ID
Description
P3.3.12
Preset Freq 1
Hz
Parameter
P1.8 or
P3.3.1
Parameter
P1.9 or P3.3.2
10
105
Defines the frequency to be used
when the following occurs:
1. PresetFreqMode (P3.3.10) is set
to Binary Coded and
Preset Freq Sel0 (P3.5.1.15) is
activated.
Preset Freq Sel1 (P3.5.1.16) is de-
activated.
Preset Freq Sel2 (P3.5.1.17) is de-
activated.
2. PresetFreqMode (P3.3.10) is set
to Number of Inputs &
Preset Freq Sel0 (3.5.1.15) is
activated.
Preset Freq Sel1 (3.5.1.16) is de-
activated.
Preset Freq Sel2 (3.5.1.17) is de-
activated.
P3.3.13
Preset Freq 2
Hz
Parameter
P1.8 or
P3.3.1
Parameter
P1.9 or P3.3.2
15
106
Defines the frequency to be used
when the following occurs:
1. PresetFreqMode (P3.3.10) is set
to Binary Coded and
Preset Freq Sel0 (P3.5.1.15) is de-
activated.
Preset Freq Sel1 (P3.5.1.16) is
activated.
Preset Freq Sel2 (P3.5.1.17) is de-
activated.
2. PresetFreqMode (P3.3.10) is set
to Number of Inputs &
Preset Freq Sel0 (P3.5.1.15) is de-
activated.
Preset Freq Sel1 (P3.5.1.16) is
activated.
Preset Freq Sel2 (P3.5.1.17) is de-
activated.
P3.3.14
Preset Freq 3
Hz
Parameter
P1.8 or
P3.3.1
Parameter
P1.9 or P3.3.2
20
126
Defines the frequency to be used
when the following occurs:
1. PresetFreqMode (P3.3.10) is set
to Binary Coded &
Preset Freq Sel0 (P3.5.1.15) is
activated.
Preset Freq Sel1 P(3.5.1.16) is
activated.
Preset Freq Sel2 (P3.5.1.17) is de-
activated.
2. PresetFreqMode (P3.3.10) is set
to Number of Inputs &
Preset Freq Sel0 (P3.5.1.15) is de-
activated.
Preset Freq Sel1 (P3.5.1.16) is de-
activated.
Preset Freq Sel2 (P3.5.1.17) is
activated.