Operating Instructions
10
Training Exercises
Exercise Answers/Information
46
Siemens Industry, Inc. 125-1007 Rev.BA
2014-08-14
Damper Control
Relay Output
– Set RO3 Function (3.5.3.2.7) to DamperLogicCtrl
NOTE:
This is configured using the Bypass Wizard.
End Switch Feedback
Digital Input
– Set Run Enable (3.5.1.11) to DigINSlotA.4
NOTE:
This is configured using the Bypass Wizard.
Safeties
Low Temp Detector
– Set Remote Safety 1 (3.5.1.44) to DigINSlotA.2
NOTE:
This is configured using the Bypass Wizard.
Smoke Sensor
– Set Remote Safety 2 (3.5.1.45) to DigINSlotA.3
NOTE:
This is configured using the Bypass Wizard.
Vibration Sensor
– Set Remote Safety 3 (3.5.1.46) to DigINSlotD.1
Exercise 6
Key information:
NOTE:
When the Bypass Wizard is run again, all I/O is reset to the defaults; so, if
safeties were programmed to different Digital Inputs or disabled completely, they will
be re-enabled as default settings.
Essential Services:
Digital Input
– Set Essential Services (3.5.1.52) to DigINSlotA.6
NOTE:
This is configured using the Bypass Wizard.
Start/Stop
Digital Input
– Set Ctrl Signal 1A (3.5.1.1) to DigINSlotA.1
NOTE:
This is configured using the Startup Wizard.
Safeties
Low Temp Detector
– Set Remote Safety 1 (3.5.1.44) to DigINSlotA.2
NOTE:
This is configured using the Bypass Wizard.
Vibration Sensor
– Set Remote Safety 2 (3.5.1.45) to DigINSlotA.3
NOTE:
This is configured using the Bypass Wizard\
Speed Reference
0 to 10 Vdc