Operating Instructions
8
Diagnostic Board
Test Points
30
Siemens Industry, Inc. 125-1007 Rev.BA
2014-08-14
Figure 18: Diagnostic Test Points.
Test
Point
Reference
Expected Voltage
Description
Drive
Off
Bypass/
Essential
Services
TP1
TP8
115 Vac 115 Vac 115 Vac Point between OL1 Terminal 96 and
M2A-B Terminal 3.
TP2 0 Vac 115 Vac 115 Vac Point between M2A-B Terminal 2
and Drive OPT-B5 card Terminal 22.
TP3 0 Vac 0 Vac 115 Vac Drive OPT-B5 card Terminal 23 (M1
coil power).
TP4 115 Vac 115 Vac 115 Vac Point between OL1 Terminal 96 and
M1A-B Terminal 3.
TP5 115 Vac 115 Vac 0 Vac Point between M1A-B terminal M2
and Drive OPT B5 card Terminal 25.
TP6 115 Vac 0 Vac 0 Vac Drive OPT-B5 card Terminal 26 (M2
coil power).
TP7 N/A N/A N/A Not used.
TP8 0 Vac 0 Vac 0 Vac Vac Neutral.