3.5.17 Group 3.16: Fire mode
The drive ignores all commands from the keypad, fieldbuses and the PC tool and runs at preset
frequency when activated. If activated, the alarm sign is shown on the keypad and the warranty is void.
In order to enable the function, you need to set a password in the description field for parameter Fire
Mode password. Please note the NC (normally closed) type of this input!
NOTE: THE WARRANTY IS VOID IF THIS FUNCTION IS ACTIVATED!
There is also a different password for test mode to be used for testing the Fire Mode without the warranty
becoming void.
3.5.18 Group 3.17: Application settings
Table 53: Fire Mode Parameters.
Code Parameter Min Max Unit Default ID Description
P3.16.1 Fire Mode password 0 9999 0 1599
1001 = Enabled
1234 = Test mode
P3.16.2 Fire Mode activation DigIN Slot0.2 1596
FALSE = Fire Mode active
TRUE = No action
P3.16.3 Fire Mode frequency 8.00 P3.3.2 Hz 0.00 1598
Frequency used when Fire
Mode is activated.
P3.16.4
Fire Mode frequency
source
0 8 0 1617
Selection of reference
source when Fire Mode is
active. This enables selec-
tion of e.g. AI1 or PID con-
troller as reference source
also while operating in Fire
Mode.
0 = Fire Mode frequency
1 = Preset speeds
2 = Keypad
3 = Fieldbus
4 = AI1
5 = AI2
6 = AI1 + AI2
7 = PID1
8 = Motor potentiometer
P3.16.5 Fire Mode reverse DigIN Slot0.1 1618
Reverse command of rota-
tion direction while running
in Fire Mode. This function
has no effect in normal
operation.
FALSE = Forward
TRUE = Reverse
P3.16.6 Fire Mode status 0 3 0 1597
Monitoring value (see also
Table )
0 = Disabled
1 = Enabled
2 = Activated (Enabled + DI
Open)
3 = Test Mode
Table 54: Application settings.
Code Parameter Min Max Unit Default ID Description
P3.17.1 Password 0 65000 0