Operating Instructions
Table Of Contents
- 1. Siemens BT300 - Startup
- 2. Keypad of the drive
- 3. Siemens Application
- 3.1 Specific functions of the Siemens application
- 3.2 Example of control connections
- 3.3 Application - Quick setup parameter group
- 3.4 Monitor group
- 3.5 Application parameter lists
- 3.5.1 Parameter programming
- 3.5.2 Column explanations
- 3.5.3 Group 3.1: Motor settings
- 3.5.4 Group 3.2: Start/Stop setup
- 3.5.5 Group 3.3: Control reference settings
- 3.5.6 Group 3.4: Ramp & Brakes Setup
- 3.5.7 Group 3.5: I/O Configuration
- 3.5.8 Group 3.6: Fieldbus Data Mapping
- 3.5.9 Group 3.7: Prohibited Frequencies
- 3.5.10 Group 3.8: Limit supervisions
- 3.5.11 Group 3.9: Protections
- 3.5.12 Group 3.10: Automatic reset
- 3.5.13 Group 3.11: Timer functions
- 3.5.14 Group 3.12: PID-controller 1
- 3.5.15 Group 3.13: PID-controller 2
- 3.5.16 Group 3.14: Multi-pump
- 3.5.17 Group 3.16: Fire mode
- 3.5.18 Group 3.17: Application settings
- 3.6 HVAC Application - Additional parameter information
- 3.7 Application - Fault tracing
Siemens Industry, Inc. • 4 Siemens BT300 - Startup
24-hour support +1-800-877-7545 (Dial 2)
Now the Startup Wizard is done.
The Startup Wizard can be re-initiated by activating the parameter Restore factory defaults
(par. P6.5.1) in the Parameter backup sub-menu (M6.5) OR with parameter P1.19 in the Quick setup
menu.
1.2 PID Mini-Wizard
The PID mini wizard is activated in the Quick Setup menu. This wizard presupposes that you are going
to use the PID controller in the "one feedback / one setpoint" mode. The control place will be I/O A and
the default process unit ‘%’.
The PID mini wizard
asks for the following values to be set:
If any other process unit than ‘%’ is selected the following questions appear: If not the Wizard will directly
jump to step 5.
If one of the analog input signals is selected the question 6 appears. Otherwise you will be taken to step
7.
If one of the analog input signals is selected the question 9 appears. Otherwise you will be taken to
question 11.
If either of the options Keypad Setpoint 1 or 2 is chosen the step 10 will appear.
9
Set value for Motor nominal current (ac-
cording to nameplate)
Range: Varies
10
Set value
for
Minimum frequency Range: 0.00...60.00 Hz
11
Set
value
for
Maximum frequency Range: 0.00...320.00 Hz
1
Process unit selection (Several selections. See par. P3.12.1.4)
2
Process unit min
3
Process unit max
4
Process unit decimals 0...4
5
Feedback 1 source selection See page 67 for selections.
6
Analog input signal range 0 = 0…10 V / 0…20 mA
1 = 2…10 V / 4…20 mA
See page 45.
7
Error inversion 0 = Normal
1 = Inverted
8
Setpoint source selection See page 61 for selections.
9
Analog input signal range 0 = 0…10 V / 0…20 mA
1 = 2…10 V / 4…20 mA
See page 45.
10
Keypad setpoint