Operating Instructions

Table Of Contents
Siemens Application Siemens Industry, Inc. • 55
24-hour support +1-800-877-7545 (Dial 2)
3
Timer 1
The manual bypassing can be handled by a digital input 1 on slot A (by a different switch or connection
to lighting).
P3.11.6.1: Duration: 1800s (30min)
P3.11.6.2: Assign to channel: Time channel 1
P3.5.1.18: Timer 1: DigIn SlotA.1 (Parameter located in digital inputs menu.)
Figure 13. Final configuration where Time channel 1 is used as control signal for
start command instead of a digital input.
Table 41: Timer functions.
Code Parameter Min Max Unit Default ID Description
3.11.1 INTERVAL 1
P3.11.1.1 ON time 00:00:00 23:59:59 hh:mm:ss 00:00:00 1464 ON time
P3.11.1.2 OFF time 00:00:00 23:59:59 hh:mm:ss 00:00:00 1465 OFF time
P3.11.1.3 From day 0 6 0 1466
ON day of week
0 = Sunday
1 = Monday
2 = Tuesday
3 = Wednesday
4 = Thursday
5 = Friday
6 = Saturday
P3.11.1.4 To day 0 6 0 1467 See above
P3.11.1.5 Assign to channel 0 3 0 1468
Select affected time channel
(1-3)
0 = Not used
1 = Time channel 1
2 = Time channel 2
3 = Time channel 3
3.11.2 INTERVAL 2
P3.11.2.1 ON time 00:00:00 23:59:59 hh:mm:ss 00:00:00 1469 See Interval 1
P3.11.2.2 OFF time 00:00:00 23:59:59 hh:mm:ss 00:00:00 1470 See Interval 1
P3.11.2.3 From day 0 6 0 1471 See Interval 1
P3.11.2.4 To day 0 6 0 1472 See Interval 1
P3.11.2.5 Assign to channel 0 3 0 1473 See Interval 1
3.11.3 INTERVAL 3
P3.11.3.1 ON time 00:00:00 23:59:59 hh:mm:ss 00:00:00 1474 See Interval 1
P
11092.emf
Interval 2
To = Sund ayFrom = Saturday
Digital input 1 on Slot A
Interval 1
Timer 1
Duration = 1800 s
To = Frid ayFrom = Monday
Ctrl Signal 1A
Time channel 1
Start/Stop
ON = 07:00:00 hs OFF = 17:00:00 hs
ON = 09:00:00 hs OFF = 13:00:00 hs