Operating Instructions

Table Of Contents
Keypad of the drive Siemens Industry, Inc. • 11
24-hour support +1-800-877-7545 (Dial 2)
2
Before any parameters can successfully be copied from one drive to another, the drive has to be stopped
when the parameters are downloaded.
First go into User settings menu and locate the Parameter backup sub-menu.
In the Parameter backup sub-menu, there are three possible functions to be selected:
Restore factory defaults will re-establish the parameter settings originally made
at the factory.
By selecting Save to keypad you can copy all parameters to the keypad.
Restore from keypad will copy all parameters from the keypad to a drive.
Figure 6. Parameter copy.
NOTE: If the keypad is changed between drives of different sizes, the copied values of these parame-
ters will not be used:
Motor nominal current (P3.1.1.4)
Motor nominal voltage (P3.1.1.1)
Motor nominal speed (P3.1.1.3)
Motor nominal power (P3.1.1.6)
Motor nominal frequency (P3.1.1.2)
Motor cos phii (P3.1.1.5)
Switching frequency (P3.1.2.1)
Motor current limit (P3.1.1.7)
Stall current limit (P3.9.12)
Stall time limit (P3.9.13)
Stall frequency (P3.9.14)
Maximum frequency (P3.3.2)
2.1.2.5 Help
The graphical keypad features instant help, and information displays for various items.
All parameters offer an instant help display. Select Help and press the OK button.
Text information is also available for faults, alarms and the startup wizard.
Figure 7. Help text example.
STOP READY Keypad
(0)
(4)
ID: M6
(8)
STOP READY Keypad
(3)
ID: M6.5M6.5
STOP READY Keypad
ID: M6.5M6.5.1
BT11088
Main Menu
Favourites
User settings
I/O and Hardware
Drive name
User settings
Application selection
HVAC
Parameter backup
Drive
Restore from keypad
Restore factory defaults
Save to keypad
Parameter backup
(6)
STOP READY I/O
ID:403 M3.5.1.1
(6)
STOP READY I/O
ID:403 M3.5.1.1
STOP READY I/O
ID:403
M3.5.1.1
BT9165
Digital Inputs
Ctrl Signal 1 A
Ctrl Signal 1 B
Ctrl Signal 2 A
Add to favorites
Ctrl signal 1 A
Edit
Help
Start Signal 1 for control Place
I/O A. Start Signal 1
functionality chosen with I/O A
Logic in Start/Stop Setup Menu.
Ctrl signal 1 A