Operating Instructions
Operation (Electronic Bypass Only)
Drive Mode
–
Hand
28
Siemens Industry, Inc. BT300 Bypass Operator's Manual DPD01391
Building Technologies 2017-09-28
4.
Use the Up and/or Down Arrow buttons to
highlight Activate, and then press OK .
The unit is now operating in the Drive mode using I/O or Fieldbus control. The display
will return to the default display.
Drive Mode – Hand
Hand
mode is used when you want to override the automation system and run the
drive in keypad mode.
● You have full control to start/stop the motor, and what the speed reference is from
the keypad directly.
● In Hand mode, the Bypass (M1) contactor is opened and the Output (M2) contactor
is closed.
1.
At the drive keypad, press the Hand/Auto button.
2.
Use the Up and/or Down Arrow buttons to
highlight Drive, and then press OK .
3.
Use the Up and/or Down Arrow buttons to
highlight Hand, and then press OK .