Operating Instructions
Table Of Contents
- 1. Siemens BT300 - Startup
- 2. Keypad of the drive
- 3. Siemens Application
- 3.1 Specific functions of the Siemens application
- 3.2 Example of control connections
- 3.3 Application - Quick setup parameter group
- 3.4 Monitor group
- 3.5 Application parameter lists
- 3.5.1 Parameter programming
- 3.5.2 Column explanations
- 3.5.3 Group 3.1: Motor settings
- 3.5.4 Group 3.2: Start/Stop setup
- 3.5.5 Group 3.3: Control reference settings
- 3.5.6 Group 3.4: Ramp & Brakes Setup
- 3.5.7 Group 3.5: I/O Configuration
- 3.5.8 Group 3.6: Fieldbus Data Mapping
- 3.5.9 Group 3.7: Prohibited Frequencies
- 3.5.10 Group 3.8: Limit supervisions
- 3.5.11 Group 3.9: Protections
- 3.5.12 Group 3.10: Automatic reset
- 3.5.13 Group 3.11: Timer functions
- 3.5.14 Group 3.12: PID-controller 1
- 3.5.15 Group 3.13: PID-controller 2
- 3.5.16 Group 3.14: Multi-pump
- 3.5.17 Group 3.16: Fire mode
- 3.5.18 Group 3.17: Application settings
- 3.6 HVAC Application - Additional parameter information
- 3.7 Application - Fault tracing
Siemens BT300 - Startup Siemens Industry, Inc. • 5
24-hour support +1-800-877-7545 (Dial 2)
If option ‘Yes’ is selected you will be prompted for three more values:
1.3 Multi-pump mini-wizard
The Multi-Pump mini-wizard asks the most important questions for setting up a Multi-Pump system. The
PID mini-wizard always precedes the Multi-Pump mini-wizard. The keypad will guide you through the
questions as in Chapter 1.2 then to be followed by the set of questions below:
If Auto-change function is enabled the following three questions will appear. If Auto-change will not be
used the Wizard jumps directly to question 11.
After this, the keypad will show the digital input and relay output configuration done by the
application. Write these values down for future reference.
11
Sleep function? No
Yes
12
Sleep frequency limit 1 0.00...320.00 Hz
13
Sleep delay 1 0...3000 s
14
Wake-up level 1 Range depends on selected process unit.
15
Number of motors 1...4
16
Interlock function 0 = Not used
1 = Enabled
17
Autochange 0 = Disabled
1 = Enabled
18
Include FC 0 = Disabled
1 = Enabled
19
Autochange interval 0.0...3000.0 h
20
Autochange: Frequency limit 0.00...60.00 Hz
21
Bandwidth 0...100%
22
Bandwidth delay 0...3600 s