Siemens Application Siemens Industry, Inc. • 51
24-hour support +1-800-877-7545 (Dial 2)
3
P3.9.19
Response to Fieldbus
communication fault
0 4 3 733 See P3.9.1
P3.9.20
Slot communication
fault
0 3 2 734 See P3.9.2
P3.9.21 Thermistor fault 0 3 0 732
See P3.9.2
It is recommended to set
this value to 2 if an option
card is installed which has
a thermistor present.
P3.9.22
Response to PID1
supervision fault
0 3 2 749 See P3.9.2
P3.9.23
Response to PID2
supervision fault
0 3 2 757 See P3.9.2
P3.9.26 TempFault Signal 0 6
Not
Used
739
Selection for which signals to
use for alarm and fault trig-
gering.
P3.9.27 TempAlarm Limit -30.0 200.0 130.0 741
Temperature for trigging an
alarm.
P3.9.28 TempAlarm Limit -30.0 200.0 155.0 742
Temperature for trigging a
fault.
P3.9.29 TempFault Response 0 3 Fault 740
Fault response for Tempera-
ture Fault.
0 = No response
1 = Alarm
2 = Fault (Stop according to
stop mode)
3 = Fault (Stop by coasting)
Table 39: Protections settings.
Code Parameter Min Max Unit Default ID Description