3.5.9 Group 3.7: Prohibited Frequencies
In some systems it may be necessary to avoid certain frequencies due to mechanical resonance prob-
lems. By setting up prohibit frequencies, it is possible to skip these ranges.
Table 37: Prohibited Frequencies.
Code Parameter Min Max Unit Default ID Description
P3.7.1
Prohibited frequency
range 1 low limit
-1,00 320,00 Hz 0,00 509 0 = Not used
P3.7.2
Prohibited frequency
range 1 high limit
0,00 320,00 Hz 0,00 510 0 = Not used
P3.7.3
Prohibited frequency
range 2 low limit
0,00 320,00 Hz 0,00 511 0 = Not used
P3.7.4
Prohibited frequency
range 2 high limit
0,00 320,00 Hz 0,00 512 0 = Not used
P3.7.5
Prohibited frequency
range 3 low limit
0,00 320,00 Hz 0,00 513 0 = Not used
P3.7.6
Prohibited frequency
range 3 high limit
0,00 320,00 Hz 0,00 514 0 = Not used
P3.7.7 Ramp time factor 0,1 10,0 Times 1,0 518
Multiplier of the currently
selected ramp time between
prohibited frequency limits.