Operating Instructions
Table Of Contents
- 1. Siemens BT300 - Startup
- 2. Keypad of the drive
- 3. Siemens Application
- 3.1 Specific functions of the Siemens application
- 3.2 Example of control connections
- 3.3 Application - Quick setup parameter group
- 3.4 Monitor group
- 3.5 Application parameter lists
- 3.5.1 Parameter programming
- 3.5.2 Column explanations
- 3.5.3 Group 3.1: Motor settings
- 3.5.4 Group 3.2: Start/Stop setup
- 3.5.5 Group 3.3: Control reference settings
- 3.5.6 Group 3.4: Ramp & Brakes Setup
- 3.5.7 Group 3.5: I/O Configuration
- 3.5.8 Group 3.6: Fieldbus Data Mapping
- 3.5.9 Group 3.7: Prohibited Frequencies
- 3.5.10 Group 3.8: Limit supervisions
- 3.5.11 Group 3.9: Protections
- 3.5.12 Group 3.10: Automatic reset
- 3.5.13 Group 3.11: Timer functions
- 3.5.14 Group 3.12: PID-controller 1
- 3.5.15 Group 3.13: PID-controller 2
- 3.5.16 Group 3.14: Multi-pump
- 3.5.17 Group 3.16: Fire mode
- 3.5.18 Group 3.17: Application settings
- 3.6 HVAC Application - Additional parameter information
- 3.7 Application - Fault tracing
Siemens Industry, Inc. • 42 Siemens Application
24-hour support +1-800-877-7545 (Dial 2)
3.5.7.2 Analog inputs
Table 30: Analog input settings.
Code Parameter Min Max Unit Default ID Description
P3.5.2.1 AI1 signal selection
AnIN
SlotA.1
377
Connect the AI1 signal to the
analog input of your choice
with this parameter.
Programmable
P3.5.2.2 AI1 signal filter time 0.00 300.00 s 1.0 378 Filter time for analog input
P3.5.2.3 AI1 signal range 0 1 0 379
0 = 0…10 V / 0…20 mA
1 = 2…10 V / 4…20 mA
P3.5.2.4 AI1 custom. min -160.00 160.00 % 0.00 380
Custom range min setting
20% = 4-20 mA/2-10 V
P3.5.2.5 AI1 custom. max -160.00 160.00 % 100.00 381 Custom range max setting
P3.5.2.6 AI1 signal inversion 0 1 0 387
0 = Normal
1 = Signal inverted
P3.5.2.7 AI2 signal selection
AnIN
SlotA.2
388 See P3.5.2.1.
P3.5.2.8 AI2 signal filter time 0.00 300.00 s 1.0 389 See P3.5.2.2.
P3.5.2.9 AI2 signal range 0 1 1 390
0 = 0…10 V / 0…20 mA
1 = 2…10 V / 4…20 mA
P3.5.2.10 AI2 custom. min -160.00 160.00 % 0.00 391 See P3.5.2.4.
P3.5.2.11 AI2 custom. max -160.00 160.00 % 100.00 392 See P3.5.2.5.
P3.5.2.12 AI2 signal inversion 0 1 0 398 See P3.5.2.6.
P3.5.2.13 AI3 signal selection
AnIN
Slot0.1
141
Connect the AI3 signal to the
analog input of your choice
with this parameter.
Programmable
P3.5.2.14 AI3 signal filter time 0.00 300.00 s 1.0 142 Filter time for analog input
P3.5.2.15 AI3 signal range 0 1 0 143
0 = 0…10 V / 0…20 mA
1 = 2…10 V / 4…20 mA
P3.5.2.16 AI3 custom. min -160.00 160.00 % 0.00 144 20% = 4-20 mA/2-10 V
P3.5.2.17 AI3 custom. max -160.00 160.00 % 100.00 145 Custom range max setting
P3.5.2.18 AI3 signal inversion 0 1 0 151
0 = Normal
1 = Signal inverted
P3.5.2.19 AI4 signal selection
AnIN
Slot0.1
152
See P3.5.2.13. Programma-
ble
P3.5.2.20 AI4 signal filter time 0.00 300.00 s 1.0 153 See P3.5.2.14.
P3.5.2.21 AI4 signal range 0 1 0 154
0 = 0…10 V / 0…20 mA
1 = 2…10 V / 4…20 mA
P3.5.2.22 AI4 custom. min -160.00 160.00 % 0.00 155 See P3.5.2.16.
P3.5.2.23 AI4 custom. max -160.00 160.00 % 100.00 156 See P3.5.2.17.
P3.5.2.24 AI4 signal inversion 0 1 0 162 See P3.5.2.18.
P3.5.2.25 AI5 signal selection
AnIN
Slot0.1
188
Connect the AI5 signal to the
analog input of your choice
with this parameter.
Programmable.
P3.5.2.26 AI5 signal filter time 0.00 300.00 s 1.0 189 Filter time for analog input
P3.5.2.27 AI5 signal range 0 1 0 190
0 = 0…10 V / 0…20 mA
1 = 2…10 V / 4…20 mA
P3.5.2.28 AI5 custom. min -160.00 160.00 % 0.00 191 20% = 4-20 mA/2-10 V