3
P3.5.1.24 PID2 select setpoint DigIN Slot0.1 1048
FALSE = Setpoint 1
TRUE = Setpoint 2
P3.5.1.25 Motor 1 interlock DigIN Slot0.1 426
FALSE = Not active
TRUE = Active
P3.5.1.26 Motor 2 interlock DigIN Slot0.1 427
FALSE = Not active
TRUE = Active
P3.5.1.27 Motor 3 interlock DigIN Slot0.1 428
FALSE = Not active
TRUE = Active
P3.5.1.28 Motor 4 interlock DigIN Slot0.1 429
FALSE = Not active
TRUE = Active
P3.5.1.30 Motor potentiometer UP DigIN Slot0.1 418
FALSE = Not active
TRUE = Active (Motor potentiometer reference
INCREASES until the contact is opened)
P3.5.1.31
Motor potentiometer
DOWN
DigIN Slot0.1 417
FALSE = Not active
TRUE = Active (Motor potentiometer reference
DECREASES until the contact is opened)
P3.5.1.32 Ramp 2 selection DigIN Slot0.1 408
Used for switching between ramp 1 and 2.
OPEN = Ramp1 shape, acceleration time 1 and
deceleration time 1.
CLOSED = Ramp2 shape, acceleration time 2
and deceleration time 2.
P3.5.1.33 Fieldbus control DigIN Slot0.1 441 TRUE = Forces control place to fieldbus.
P3.5.1.34 Fire mode reverse DigIN Slot0.1 1618
Reverse command of rotation direction while run-
ning in Fire Mode. This function has no effect in
normal operation.
FALSE = Forward
TRUE = Reverse
P3.5.1.43 ResetkWhTripCounter DigIN Slot0.1 1053 Reset kWh Trip Counter
Table 29: Digital input settings.