Operating Instructions
Training Exercises
10
Exercise Answers/Information
45
Siemens Industry, Inc. 125-1007 Rev.BA
2014-08-14
Operation
Airflow setpoint is 45 l/s
– Set SP1 Source (3.12.2.4) to Keypad SP1
– Set Keypad SP1 (3.12.2.1) to 45
NOTE:
These are configured using the PID-Mini Wizard.
Standby once under 9hz for 30 seconds
– Set SP1 Sleep Freq (3.12.2.7) to 9
– Set SP1 Sleep Delay (3.12.2.8) to 30
NOTE:
These are configured using the PID-Mini Wizard.
Wake level under 35 l/s
– Set SP1 WakeUpLevel (3.12.2.9) to 35
NOTE:
This is configured using the PID-Mini Wizard.
Exercise 4
Key information:
NOTE:
Use the Bypass Wizard to complete the setup for the Electronic Bypass.
Start/Stop
Use Digital Input 1
– Set Ctrl Signal 1A (3.5.1.1) to DigINSLotA.1
NOTE:
This is configured using the Startup Wizard.
Safeties
Low Temp Detector - Use Digital Input 2
– Set Remote Safety 1 (3.5.1.44) to DigINSlotA.2
NOTE:
This is configured using the Bypass Wizard.
Smoke Sensor - Use Digital Input 3
– Set Remote Safety 2 (3.5.1.45) to DigINSlotA.3
NOTE:
This is configured using the Bypass Wizard.
Speed Reference
4 to 20mA on Ai2
– Set I/O A Ctrl Ref (3.3.3) to AI2
– Set AI2 Signal Range (3.5.2.9) to 2-10V/4-20mA
NOTE:
These are configured using the Startup Wizard.
Electronic Bypass
Set ByPass (3.17.4) to Electronic
NOTE:
This is configured using the Startup Wizard.
Exercise 5
Key information:
NOTE:
Use the Bypass Wizard to complete the setup for the Interlock application.