Operating Instructions

Table Of Contents
Siemens Industry, Inc. • 80 Siemens Application
24-hour support +1-800-877-7545 (Dial 2)
NOTE: Long filtering time makes the regulation response slower!
Figure 21. AI1 signal filtering.
Basic R01 function (P3.5.3.2.1)
Table 56. Output signals via RO1.
Selection Selection name Description
0 Not used
1 Ready The variable frequency drive is ready to operate
2 Run The variable frequency drive operates (motor is running)
3 General fault A fault trip has occurred
4 General fault inverted A fault trip has not occurred
5 General alarm
6 Reversed The reverse command has been selected
7 At speed The output frequency has reached the set reference
8 Motor regulator activated
One of the limit regulators (e.g. current limit, torque limit) is acti-
vated
9 Preset frequency active The preset
frequency
has been selected with digital input
10 Keypad control active Keypad control mode selected
11 I/O control B active I/O control place B selected
12 Limit supervision 1
Activates if the signal value falls below or exceeds the set super-
vision limit (P3.8.3 or P3.8.7) depending on the selected function.
13 Limit supervision 2
14 Start command active Start command is active.
15 Reserved
16 Fire mode ON
17 RTC timer 1 control Time channel 1 is used.
18 RTC timer 2 control Time channel 2 is used.
19 RTC timer 3 control Time channel 3 is used.
20 FB Control WordB.13
21 FB Control WordB.14
22 FB Control WordB.15
23 PID1 in Sleep mode
%
100%
63%
P3.5.2.2
t [s]
11097.emf
Fil tered signal
Unfiltered signal