Operating Instructions
Table Of Contents
- 1. Siemens BT300 - Startup
- 2. Keypad of the drive
- 3. Siemens Application
- 3.1 Specific functions of the Siemens application
- 3.2 Example of control connections
- 3.3 Application - Quick setup parameter group
- 3.4 Monitor group
- 3.5 Application parameter lists
- 3.5.1 Parameter programming
- 3.5.2 Column explanations
- 3.5.3 Group 3.1: Motor settings
- 3.5.4 Group 3.2: Start/Stop setup
- 3.5.5 Group 3.3: Control reference settings
- 3.5.6 Group 3.4: Ramp & Brakes Setup
- 3.5.7 Group 3.5: I/O Configuration
- 3.5.8 Group 3.6: Fieldbus Data Mapping
- 3.5.9 Group 3.7: Prohibited Frequencies
- 3.5.10 Group 3.8: Limit supervisions
- 3.5.11 Group 3.9: Protections
- 3.5.12 Group 3.10: Automatic reset
- 3.5.13 Group 3.11: Timer functions
- 3.5.14 Group 3.12: PID-controller 1
- 3.5.15 Group 3.13: PID-controller 2
- 3.5.16 Group 3.14: Multi-pump
- 3.5.17 Group 3.16: Fire mode
- 3.5.18 Group 3.17: Application settings
- 3.6 HVAC Application - Additional parameter information
- 3.7 Application - Fault tracing
Siemens Application Siemens Industry, Inc. • 67
24-hour support +1-800-877-7545 (Dial 2)
3
3.5.15.3 Feedback
For more detailed information, see Chapter 3.5.14.
3.5.15.4 Process supervision
For more detailed information, see Chapter 3.5.14.
Table 50: PID-2 Feedback
Code Parameter Min Max Unit Default ID Description
P3.13.3.1 Feedback function 1 9 1 1650
Choose a single signal used
as feedback or make calcula-
tions
based on one or two signals.
P3.13.3.2
Feedback function
gain
-1000.0 1000.0 % 100.0 1651
Feedback Gain is added
after the feedback function
(parameter) before fed
straight to the PID.
P3.13.3.3
Feedback 1
source selection
0 14 1 1652
Select from where we should
take the signal for this
feedback. Notice! Process-
DataIn uses two decimals as
format.
P3.13.3.4 Feedback 1 minimum -200.00 200.00 % 0.00 1653
Minimum value at analog sig-
nal minimum.
P3.13.3.5 Feedback 1 maximum -200.00 200.00 % 100.00 1654
Maximum value at analog
signal maximum.
P3.13.3.6
Feedback 2
source selection
0 14 2 1655
Select from where we should
take the signal for this feed-
back. Notice! ProcessDataIn
uses two decimals as format.
P3.13.3.7 Feedback 2 minimum -200.00 200.00 % 0.00 1656
Minimum value at analog sig-
nal minimum.
P3.13.3.8 Feedback 2 maximum -200.00 200.00 % 100.00 1657
Maximum value at analog
signal maximum.
Table 51: PID-2 Process Supervision.
Code Parameter Min Max Unit Default ID Description
P3.13.4.1 Enable supervision 0 1 0 1659
0 = Disabled
1 = Enabled
P3.13.4.2 Upper limit Varies Varies Varies Varies 1660
Process supervision is
used to supervise that the
actual value stays within
some predefined limits. With
this function we can e.g.
detect a major pipe burst and
stop unnecessary flooding.
An upper and lower limit for
the supervision range can be
set, including a delay when
trigging faults.