Operating Instructions
Table Of Contents
- 1. Siemens BT300 - Startup
- 2. Keypad of the drive
- 3. Siemens Application
- 3.1 Specific functions of the Siemens application
- 3.2 Example of control connections
- 3.3 Application - Quick setup parameter group
- 3.4 Monitor group
- 3.5 Application parameter lists
- 3.5.1 Parameter programming
- 3.5.2 Column explanations
- 3.5.3 Group 3.1: Motor settings
- 3.5.4 Group 3.2: Start/Stop setup
- 3.5.5 Group 3.3: Control reference settings
- 3.5.6 Group 3.4: Ramp & Brakes Setup
- 3.5.7 Group 3.5: I/O Configuration
- 3.5.8 Group 3.6: Fieldbus Data Mapping
- 3.5.9 Group 3.7: Prohibited Frequencies
- 3.5.10 Group 3.8: Limit supervisions
- 3.5.11 Group 3.9: Protections
- 3.5.12 Group 3.10: Automatic reset
- 3.5.13 Group 3.11: Timer functions
- 3.5.14 Group 3.12: PID-controller 1
- 3.5.15 Group 3.13: PID-controller 2
- 3.5.16 Group 3.14: Multi-pump
- 3.5.17 Group 3.16: Fire mode
- 3.5.18 Group 3.17: Application settings
- 3.6 HVAC Application - Additional parameter information
- 3.7 Application - Fault tracing
Siemens Industry, Inc. • 24 Siemens Application
24-hour support +1-800-877-7545 (Dial 2)
3.4 Monitor group
The Siemens BT300 drive provides you with a possibility to monitor the actual values of parameters and
signals as well as status and measurements. Some of the values to be monitored are customizable.
3.4.1 Multi-monitor
On the multi-monitor page, you can collect nine values that you wish to monitor. See page 14 for more
information.
P1.6 Motor nominal power Varies Varies kW Varies 116
Find this value I
n
on the rat-
ing plate of the motor.
P1.7 Motor current limit Varies Varies A Varies 107
Maximum motor current
from drive.
P1.8 Minimum frequency 0.00 P3.3.1 Hz Varies 101
Minimum allowed frequency
reference.
P1.9 Maximum frequency P3.3.1 320.00 Hz 60.00 102
Maximum allowed frequency
reference.
P1.10
I/O control reference A
selection
18 6117
Selection of ref source when
control place is I/O A. See
page 37 for selections.
P1.11 Preset frequency 1 P3.3.1 300.00 Hz 10.00 105
Select with digital input:
Preset frequency selection 0
(P3.5.1.15)
P1.12 Preset frequency 2 P3.3.1 300.00 Hz 15.00 106
Select with digital input:
Preset frequency selection 1
(P3.5.1.16)
P1.13 Acceleration time 1 0.1 3000.0 s 20.0 103
Time to accelerate from zero
to maximum frequency.
P1.14 Deceleration time 1 0.1 3000.0 s 20.0 104
Time to decelerate from min-
imum to zero frequency.
P1.15 Auto control place 1 2 1 172
Selection of Auto control
place (start/stop)
1 = I/O
2 = Fieldbus
P1.16 Automatic reset 0 1 0 731
0 = Disabled
1 = Enabled
P1.17 PID Mini-Wizard 0 1 0 1803
0 = Inactive
1 = Activate
See Chapter 1.2.
P1.18 Multi-Pump Wizard 0 1 0
0 = Inactive
1 = Activate
See Chapter 1.3.
P1.19 Startup Wizard 0 1 0 1171
0 = Inactive
1 = Activate
See Chapter 1.1.
Table 14: Quick setup parameter group.
Code Parameter Min Max Unit Default ID Description