2019-05-29
Timer 3 (M3.11.8)
Table 54: Timer 3.
Structure
Parameter
Unit
Min
Max
Default
ID
Description
P3.11.8.1
Duration
s
0
72000
0
1491
See description for P3.11.6.1
P3.11.8.2
AssignToChannel
Not Used
Time Channel 3
Not Used
1494
See description for P3.11.6.2
Example
Problem:
We have a variable frequency drive for air conditioning in a warehouse. It needs to run between 7:00 A.M. until
5:00 P.M. on weekdays, and 9:00 A.M. until 1:00 P.M. on weekends. Additionally, the drive must be manually
forced to run outside working hours if there are people in the building, and must continue to run for 30
minutes afterwards.