Operating Instructions
Table Of Contents
- 1. Siemens BT300 - Startup
- 2. Keypad of the drive
- 3. Siemens Application
- 3.1 Specific functions of the Siemens application
- 3.2 Example of control connections
- 3.3 Application - Quick setup parameter group
- 3.4 Monitor group
- 3.5 Application parameter lists
- 3.5.1 Parameter programming
- 3.5.2 Column explanations
- 3.5.3 Group 3.1: Motor settings
- 3.5.4 Group 3.2: Start/Stop setup
- 3.5.5 Group 3.3: Control reference settings
- 3.5.6 Group 3.4: Ramp & Brakes Setup
- 3.5.7 Group 3.5: I/O Configuration
- 3.5.8 Group 3.6: Fieldbus Data Mapping
- 3.5.9 Group 3.7: Prohibited Frequencies
- 3.5.10 Group 3.8: Limit supervisions
- 3.5.11 Group 3.9: Protections
- 3.5.12 Group 3.10: Automatic reset
- 3.5.13 Group 3.11: Timer functions
- 3.5.14 Group 3.12: PID-controller 1
- 3.5.15 Group 3.13: PID-controller 2
- 3.5.16 Group 3.14: Multi-pump
- 3.5.17 Group 3.16: Fire mode
- 3.5.18 Group 3.17: Application settings
- 3.6 HVAC Application - Additional parameter information
- 3.7 Application - Fault tracing
Siemens Industry, Inc. • 66 Siemens Application
24-hour support +1-800-877-7545 (Dial 2)
3.5.15.2 Setpoints
P3.13.1.12 Dead band delay 0.00 320.00 s 0.00 1638
Dead band around the
setpoint. When we are
within this area the PID
controller output will be
locked. The size of the Dead
Band area around the set-
point is set in process units.
I.e. 2 bar will give us a dead
band of +- 2bar around the
setpoint.
We can also set a delay
Table 49: PID-2 Setpoints.
Code Parameter Min Max Unit Default ID Description
P3.13.2.1 Keypad setpoint 1 0.00 100.00 Varies 0.00 1640
Setpoint in process unit that
can be selected as setpoint
source (parameters).
P3.13.2.2 Keypad setpoint 2 0.00 100.00 Varies 0.00 1641
Setpoint in process unit that
can be selected as setpoint
source (parameters).
P3.13.2.3 Setpoint ramp time 0.00 300.00 s 0.00 1642
Sometimes we don’t want
to make fast step changes
in the setpoint because it
might upset the process.
Then we can set a ramping
time for the setpoint. The
time set with this parameter
is the time it takes for the set-
point to change from 0% to
100%. NOTICE! When start-
ing the drive the setpoint
will always ramp from the
feedback value to the set-
point.
P3.13.2.4
Setpoint source 1
selection
0 16 1 1643
Select from where we should
take the signal for this set-
point.
Notice! ProcessDataIn uses
two decimals as format.
P3.13.2.5 Setpoint 1 minimum -200.00 200.00 % 0.00 1644
Minimum value at analog sig-
nal minimum.
P3.13.2.6 Setpoint 1 maximum -200.00 200.00 % 100.00 1645
Maximum value at analog
signal maximum.
P3.13.2.7
Setpoint source 2
selection
0 16 0 1646 See P3.13.2.4.
P3.13.2.8 Setpoint 2 minimum -200.00 200.00 % 0.00 1647
Minimum value at analog sig-
nal minimum.
P3.13.2.9 Setpoint 2 maximum -200.00 200.00 % 100.00 1648
Maximum value at analog
signal maximum.
Table 48: PID-2 Basic Settings.