Operating Instructions

Table Of Contents
Siemens Industry, Inc. • 34 Siemens Application
24-hour support +1-800-877-7545 (Dial 2)
3.5.3 Group 3.1: Motor settings
3.5.3.1 Basic Settings
3.5.3.2 Motor Control Settings
Table 24: Basic motor settings.
Code Parameter Min Max Unit Default ID Description
P3.1.1.1 Motor nominal voltage Varies Varies V Varies 110
Find this value U
n
(V) on the
rating plate of the motor.
This parameter sets the volt-
age at the field weakening
point to 100% * U
n
(V)
Motor
.
Note also used connection
(Delta/Star).
P3.1.1.2
Motor nominal fre-
quency
8.00 320.00 Hz Varies 111
Find this value f
n
on the rat-
ing plate of the motor.
P3.1.1.3 Motor nominal speed 24 19200 rpm Varies 112
Find this value n
n
on the rat-
ing plate of the motor.
P3.1.1.4 Motor nominal current Varies Varies A Varies 113
Find this value I
n
on the rat-
ing plate of the motor.
P3.1.1.5 Motor Cos Phi 0.30 1.00 Varies 120
Find this value on the rating
plate of the motor
P3.1.1.6 Motor nominal power Varies Varies kW Varies 116
Find this value In on the rat-
ing plate of the motor.
P3.1.1.7 Motor current limit Varies Varies A Varies 107
Maximum motor current
from drive.
P3.1.1.8 Motor type 0 1 0 650
Select what motor type is
used. 0 = asynchronous
induction motor,
1 = PM synchronous motor.
Table 25: Advanced motor settings.
Code Parameter Min Max Unit Default ID Description
P3.1.2.1 Switching frequency 1.5 Varies kHz Varies 601
Motor noise can be mini-
mized using a high switch-
ing frequency. Increasing
the switching frequency
reduces the capacity of the
drive. It is recommended to
use a lower frequency when
the motor cable is long in
order to minimize capaci-
tive currents in the cable.
P3.1.2.2 Motor switch 0 1 0 653
Enabling this function pre-
vents the drive from tripping
when the motor switch is
closed and opened using
flying start for example.
0 = Disabled
1 = Enabled
P3.1.2.4 Zero frequency voltage 0.00 40.00 % Varies 606
This parameter defines the
zero frequency voltage of
the U/f curve. The default
value varies according to
unit size.