Operating Instructions

10
Training Exercises
Exercise Answers/Information
44
Siemens Industry, Inc. 125-1007 Rev.BA
2014-08-14
Use 0.2A current
Set Preheat Current (3.1.2.7) TO 0.2
Speed Reference
Use AI1
Set I/O A Ctrl Ref (3.3.3) to AI1
NOTE:
This is configured using the Startup Wizard.
2 to 10V Signal
Set AI1 Signal Range (3.5.2.3) to 2-10V/4-20mA
NOTE:
This is configured using the Startup Wizard.
Magnetize Motor
On Start for 3s
Set StarMagnTime (3.4.7) to 3
0.3A DC current
Set MagnCurrent (3.4.8) to .37
Enable Fan Interlock Function
Enable Interlock
Set InterlockStart (3.2.9) to Enabled.
Damper activation on Relay Output 3
Set RO3 Function (3.5.3.2.7) to DamperLogicCtrl
End switch feedback on Digital Input 6
Set Run Interlock 1 (3.5.1.12) to DIGINSlotA.6
Exercise 3
Key information:
NOTE:
Use the PID-Mini Wizard to complete the setup for the Air Sensor and the PID
settings.
NOTE:
There are several parameters that are changed via the PID-Mini Wizard. The
following are just a few of the parameters that are addressed during the configuration.
Air Sensor
Connected to AI2
Set IO A Ctrl Ref (3.3.3) to A12
NOTE:
This is configured using the PID-Mini Wizard.
4 to 20mA
Set AI1 Signal Range (3.5.2.3) to 2-10V/4-20mA
NOTE:
This is configured using the PID-Mini Wizard.
10 to 150 l/s
Set ProcessUnitSel. (3.12.1.4) to I/s
Set ProcessUnitMin (3.12.1.5) to 10
Set ProcessUnitMax (3.12.1.6) to 150
NOTE:
These are configured using the PID-Mini Wizard.