3.5.14.3 Feedback
P3.12.2.12 Setpoint 2 minimum -200.00 200.00 % 0.00 1073
Minimum value at analog sig-
nal minimum.
P3.12.2.13 Setpoint 2 maximum -200.00 200.00 % 100.00 1074
Maximum value at analog
signal maximum.
P3.12.2.14
Sleep frequency limit
2
0.00 320.00 Hz 0.00 1075 See P3.12.2.7.
P3.12.2.15 Sleep delay 2 0 3000 s 0 1076 See P3.12.2.8.
P3.12.2.16 Wake-up level 2 Varies 0.0000 1077 See P3.12.2.9.
P3.12.2.17 Setpoint 2 boost -2.0 2.0 Varies 1.0 1078 See P3.12.2.10.
Table 44: PID Feedback.
Code Parameter Min Max Unit Default ID Description
P3.12.3.1 Feedback function 1 9 1 333
1 = Only Source1 in use
2 =
SQRT(Source1);(Flow=Con-
stant x SQRT(Pressure))
3 = SQRT(Source1- Source 2)
4 = SQRT(Source 1) + SQRT
(Source 2)
5 = Source 1 + Source 2
6 = Source 1 - Source 2
7 = MIN (Source 1, Source 2)
8 = MAX (Source 1, Source 2)
9 = MEAN (Source 1, Source
2)
P3.12.3.2 Feedback function gain -1000.0 1000.0 % 100.0 1058
Used e.g. with selection 2 in
Feedback function
P3.12.3.3
Feedback 1 source
selection
0 14 2 334
0 = Not used
1 = AI1
2 = AI2
3 = AI3
4 = AI4
5 = AI5
6 = AI6
7 = ProcessDataIn1
8 = ProcessDataIn2
9 = ProcessDataIn3
10 = ProcessDataIn4
11 = ProcessDataIn5
12 = ProcessDataIn6
13 = ProcessDataIn7
14 = ProcessDataIn8
AI’s and ProcessDataIn are
handled as % (0.00-100.00%)
and scaled according to Feed-
back min and max.
NOTE: ProcessDataIn use
two decimals.
P3.12.3.4 Feedback 1 minimum -200.00 200.00 % 0.00 336
Minimum value at analog sig-
nal minimum.
P3.12.3.5 Feedback 1 maximum -200.00 200.00 % 100.00 337
Maximum value at analog sig-
nal maximum.
Table 43: PID Setpoints.
Code Parameter Min Max Unit Default ID Description