Operating Instructions
3
Demonstration Panel Overview
Operation Overview
12
Siemens Industry, Inc. 125-1007 Rev.BA
2014-08-14
Configuration - Drive Only
The BT300 Variable Frequency Drive and Bypass Demonstration Panel can be used to
demonstrate the features and functions of the stand alone BT300 Drive. When used in
this manner, the Service Switch (M3) must be turned on, and, the Mode Switch must
be in the
VFD position to allow the motor to operate.
The BT300-OPT-B1-V I/O expansion board is installed in the unit. There is no default
programming associated to this I/O card. It can be freely mapped. However, all six
DIOs have been wired as digital inputs only.
The VFD only configuration uses the following I/O default values (after a factory reset):
I/O Default Value
Description
DI1 Start Forward
DI2 Start Reverse
DI3 External Fault
DI4 Preset Freq 1
DI5 Preset Freq 2
DI6 Fault Reset
AI1 0 to 10 Vdc
AI2 4 to 20 mA
RO1 Run
RO2 Fault
RO3 Ready
AO1 Output Frequency