3.4.3 Timer functions monitoring
Here you can monitor values of timer functions and the Real Time Clock.
V2.2.22
Motor current with 1 deci-
mal
45
Motor current monitor value with a fixed number
of decimals and less filtering. Can be used e.g.
for fieldbus purposes to always get the right
value regardless of frame size, or monitoring
when less filtering time is needed for the motor
current.
V2.2.23 Appl.StatusWord 1 89
Bit coded Application Status Word 1.
B0 = Interlock1
B1 = Interlock2
B5 = I/O A Control Act.
B6 = I/O B Control Act.
\fB7 = Fieldbus Control Act.
B8 = Hand Control Act.
B9 = PC Control Act.
B10 = Preset Frequencies Act.
B12 = FireMode Act.
B13 = PreHeat Act
V2.2.24 Appl.StatusWord 2 90
Bit coded Application Status Word 2.
B0 = Acc/Dec Prohibited
B1 = MotorSwitch Act.
V2.2.25 kWhTripCounter Low 1054 Energy counter with kWh output. (Low Word)
V2.2.26 kWhTripCounter High 1067
Determines how many times energy counter
has spun around. (High Word)
Table 16: Monitoring of timer functions.
Code Monitoring value Unit ID Description
V2.3.1 TC 1, TC 2, TC 3 1441
Possible to monitor the statuses of the three
Time Channels (TC)
V2.3.2 Interval 1 1442 Status of timer interval
V2.3.3 Interval 2 1443 Status of timer interval
V2.3.4 Interval 3 1444 Status of timer interval
V2.3.5 Interval 4 1445 Status of timer interval
V2.3.6 Interval 5 1446 Status of timer interval
V2.3.7 Timer 1 s 1447 Remaining time on timer if active
V2.3.8 Timer 2 s 1448 Remaining time on timer if active
V2.3.9 Timer 3 s 1449 Remaining time on timer if active
V2.3.10 Real time clock 1450
Table 15: Monitoring menu items.
Code Monitoring value Unit ID Description