Operating Instructions
Table Of Contents
- 1. Siemens BT300 - Startup
- 2. Keypad of the drive
- 3. Siemens Application
- 3.1 Specific functions of the Siemens application
- 3.2 Example of control connections
- 3.3 Application - Quick setup parameter group
- 3.4 Monitor group
- 3.5 Application parameter lists
- 3.5.1 Parameter programming
- 3.5.2 Column explanations
- 3.5.3 Group 3.1: Motor settings
- 3.5.4 Group 3.2: Start/Stop setup
- 3.5.5 Group 3.3: Control reference settings
- 3.5.6 Group 3.4: Ramp & Brakes Setup
- 3.5.7 Group 3.5: I/O Configuration
- 3.5.8 Group 3.6: Fieldbus Data Mapping
- 3.5.9 Group 3.7: Prohibited Frequencies
- 3.5.10 Group 3.8: Limit supervisions
- 3.5.11 Group 3.9: Protections
- 3.5.12 Group 3.10: Automatic reset
- 3.5.13 Group 3.11: Timer functions
- 3.5.14 Group 3.12: PID-controller 1
- 3.5.15 Group 3.13: PID-controller 2
- 3.5.16 Group 3.14: Multi-pump
- 3.5.17 Group 3.16: Fire mode
- 3.5.18 Group 3.17: Application settings
- 3.6 HVAC Application - Additional parameter information
- 3.7 Application - Fault tracing
Siemens Industry, Inc. • 22 Siemens Application
24-hour support +1-800-877-7545 (Dial 2)
3.2 Example of control connections
Table 11. Connection example, standard I/O board.
Standard I/O board
Terminal Signal Default
1 +10 Vref Reference output
2AI1+
Analog input,
voltage or current
*
*
Selectable with DIP switches, see Siemens BT300 Installa-
tion Manual
Voltage
3 AI1- Analog input common (current)
4AI2+
Analog input,
voltage or current
Current
5 AI2- Analog input common (current)
6 24Vout 24V aux. voltage
7 GND I/O ground
8 DI1 Digital input 1 Start FWD
9 DI2 Digital input 2 Start REV
10 DI3 Digital input 3 Fault
11 CM
Common A for DIN1-DIN6
**
**
Digital inputs can be isolated from ground. See Installation
Manual.
12 24Vout 24V aux. voltage
13 GND I/O ground
14 DI4 Digital input 4
Preset freq
select 1
15 DI5 Digital input 5
Preset freq
select 2
16 DI6 Digital input 6 Fault reset
17 CM Common A for DIN1-DIN6**
18 AO1+ Analog signal (+output)
Output fre-
quency
19 AO-/GND Analog output common
30 +24 Vin 24V auxiliary input voltage
ARS485
Serial bus, negative
BRS485 Serial bus, positive
Reference potentiometer
1...10 kW
Remote reference
4...20mA/0...10V
(programmable)
mA
To Relay board
1 or 2