Operating Instructions
Table Of Contents
- 1. Siemens BT300 - Startup
- 2. Keypad of the drive
- 3. Siemens Application
- 3.1 Specific functions of the Siemens application
- 3.2 Example of control connections
- 3.3 Application - Quick setup parameter group
- 3.4 Monitor group
- 3.5 Application parameter lists
- 3.5.1 Parameter programming
- 3.5.2 Column explanations
- 3.5.3 Group 3.1: Motor settings
- 3.5.4 Group 3.2: Start/Stop setup
- 3.5.5 Group 3.3: Control reference settings
- 3.5.6 Group 3.4: Ramp & Brakes Setup
- 3.5.7 Group 3.5: I/O Configuration
- 3.5.8 Group 3.6: Fieldbus Data Mapping
- 3.5.9 Group 3.7: Prohibited Frequencies
- 3.5.10 Group 3.8: Limit supervisions
- 3.5.11 Group 3.9: Protections
- 3.5.12 Group 3.10: Automatic reset
- 3.5.13 Group 3.11: Timer functions
- 3.5.14 Group 3.12: PID-controller 1
- 3.5.15 Group 3.13: PID-controller 2
- 3.5.16 Group 3.14: Multi-pump
- 3.5.17 Group 3.16: Fire mode
- 3.5.18 Group 3.17: Application settings
- 3.6 HVAC Application - Additional parameter information
- 3.7 Application - Fault tracing
Siemens Application Siemens Industry, Inc. • 99
24-hour support +1-800-877-7545 (Dial 2)
3
44 430
Device changed
(different type)
Option board changed for one not present
in the same slot before. No parameter set-
tings are saved.
Set the option board parameters
again.
45 440
Device changed
(different type)
Option board added. The option board
was not previously present in the same
slot. No parameter settings are saved.
Set the option board parameters
again.
51 1051 External fault Digital input.
52
1052
1352
Keypad commu-
nication fault
The connection between the control key-
pad and variable frequency drive is bro-
ken
Check keypad connection and possi-
ble keypad cable
53 1053
Fieldbus commu-
nication fault
The data connection between the fieldbus
master and fieldbus board is broken
Check installation and fieldbus mas-
ter.
54
1354 Slot A fault
Defective option board or slot. Check board and slot.
1454 Slot B fault
1654 Slot D fault
1754 Slot E fault
65 1065
PC communica-
tion fault
The data connection between the PC and
variable frequency drive is broken.
66 1066 Thermistor fault
The thermistor input has detected an
increase of motor temperature.
Check motor cooling and load.
Check thermistor connection
(If thermistor input is not in use it has
to be short circuited)
69
1310
Fieldbus map-
ping error
Non-existing ID number is used for map-
ping values to Fieldbus Process Data Out.
Check parameters in Fieldbus Data
Mapping menu (Chapter 3.5.8).
1311
Not possible to convert one or more val-
ues for Fieldbus Process Data Out.
The value being mapped may be of
undefined type. Check parameters in
Fieldbus DataMapping menu
(Chapter 3.5.8).
1312
Overflow when mapping and converting
values for Fieldbus Process Data Out (16-
bit).
101 1101
Process supervi-
sion fault (PID1)
PID controller: Feedback value outside of
supervision limits (and the delay if set).
105 1105
Process supervi-
sion fault (PID2)
PID controller: Feedback value outside of
supervision limits (and delay, if set).
Table 57. Fault codes and descriptions.
Fault
code
Fault
ID
Fault name Possible cause Remedy