User Manual
CA1N1985E / 11.1998 Siemens Building Technologies
2/2 Landis & Staefa Division
The adjustment range can be limited mechanically to the desired range by adjusting the
two end stops (see mounting instructions).
Resistance range 995 ...1185 Ohm (0 K = 1091 Ohm)
Materials
Cover and base plate Polycarbonate / ABS
Dial Polycarbonate / ABS
Colour
Cover plate RAL 7035 (light grey)
Dial RAL 7001 (silver grey)
Connection terminals Screw terminals for 2.5 mm
2
wire
Max. length of cable between BSGN-U1 and controller
With 0.25 mm
2
Cu 40 m
With 0.50 mm
2
Cu 75 m
With 1.0 mm
2
Cu 110 m
Weight (including packaging) 0.06 kg
Dimensions (W x H x D) 48 x 48 x 46 mm
General ambient conditions
Conditions of use For indoor use
Ambient temperature
– Operation 0 ... 55 °C
– Storage / Transport – 25 ... 70 °C
Ambient humidity < 95 %rh, non-condensing
Product safety EN60730-1
Protection class III
Protection standard (when installed) IP42 to EN60529
Conformity Meets the requirements for CE marking
40588
1
2
3
4
All dimensions in mm
70197
15 31 48
48
Drilling diagram
930180 A
14
14
ø 7ø 3,5 ø 3,5
Commissioning
Technical data
Connection terminals
Dimensions
1998 Siemens Building Technologies Ltd.