User Manual

CA1N1989E / 11.1998 Siemens Building Technologies
2/2 Landis & Staefa Division
The adjustment range can be limited mechanically by adjusting the two pins on the
fixing plate (see mounting instructions).
Resistance range See Ni1000 resistance table
Materials
Cover plate and base plate Polycarbonate / ABS
Dial Polycarbonate / ABS
Colour
Cover plate RAL 7035 (light grey)
Dial RAL 7001 (silver grey)
Connection terminals Screw terminals for 2.5 mm
2
wire
Max. length of cable between BSGN-T... and controller
With 0.25 mm
2
Cu 40 m
With 0.50 mm
2
Cu 75 m
With 1.0 mm
2
Cu 110 m
Weight (including packaging) 0.06 kg
Dimensions (W x H x D) 48 x 48 x 46 mm
General ambient conditions
Conditions of use For indoor use
Ambient temperature
– Operation 0 ... 55 °C
– Storage / Transport – 25 ... 70 °C
Ambient humidity < 95 %rh, non-condensing
Product safety EN60730-1
Protection class III
Protection standard (when installed) IP42 to EN60529
Conformity Meets the requirements for CE marking
40588
1
2
3
4
All dimensions in mm
70197
15 31 48
48
Drilling diagram
930180 A
14
14
ø 7ø 3,5 ø 3,5
Commissioning
Technical data
Connection
terminals
Dimensions
1998 Siemens Building Technologies Ltd.