User Manual

Siemens Building Technologies CM2N8882en / 02.2000
Landis & Staefa Division 1/8
8
882
VISONIK
®
I/O module points
Function sheet
All information points in a VISONIK system establishing a connection between the
building services system and the BPS by means of I/O modules and P-bus are
called "I/O module points". They fulfil the physical basic functions: Signalling,
measuring, counting, and positioning.
The following illustration shows a few typical I/O module points:
MLST
SB
MW
BPS
ZW
P-bus
I/O modules
Point types
8882Z01E
I/O module points and I/O modules in VISONIK are differentiated by their physical basic
functions and the information in data points is imaged from the associated point type.
The I/O modules transform the signals of the associated transmitters in the plant to
uniform signals of the BPS and vice versa. The following table provides an overview of
the points and signals:
I/O module points Point
type
Signal Transmitter in the plant (examples)
Signalling points ML Digital Input Contact for frost protection thermostat
Measuring points MW Analogue Input Resistance signal from the sensor
Counting points ZW Counter Input Counting pulse transmitter for flow
Switching points SB Digital Output Switching contactor for fan
Positioning points SE Analogue Output Fan actuator with positioning input of
0..10 V
The following pages contain descriptions of the individual I/O module points.
Use
Example
Explanation

Summary of content (8 pages)