Menu-guided operation in the VISONIK BPS uses dialog procedures. A selection is
always displayed on-screen. The selection contains other menus as well as changeable
states and values. The following screenshots provide an overview of both functionality
and operation.
After establishing connection and entering the password for KEY1 or KEY2, the BPS
opens the main menu. The desired submenu can then be selected by entering the
associated number or letter:
OpD 11:41:53 B P S O P E R A T I N G D I A L O G 17-JUL-1996/WE
MENU Q End
1 Group1 North heating
1 Group2 South heating
2 Group3 Office air cond.
P Reports
S Special days SDC
OpD 11:41:53 B P S O P E R A T I N G D I A L O G 17-JUL-1996/WE
Select ...:
The following picture shows the group menu for group 3 „AirCondOffice”. Enter all
operations for this plant in this menu: From plant control to setpoint adjustments to
changes of the timeswitch program.
OpD 16:18:42 B P S O P E R A T I N G D I A L O G 17-JUL-1996/WE
MENU * Group 3 AirCondOffice *
Q Quit
1 Control Auto Actual Status Off
2 Setpoints/Defaults
Heating 20 / 12 degrees C
Cooling 22 / 28 degrees C
2 Parameter
Supply Air, minimum 16 degrees C
3 Unlock Group
4 Refresh Screen
5 Weekday Catalogue WDC
6 Exception Catalogue EXC
7 Todays Op. Time Change RTC
OpD 16:18:13 B P S O P E R A T I N G D I A L O G 17-JUL-1996/WE
Select ...:
The operating dialog for changing plant control and operating state is used in this
example. The plant is to be set from „Auto/OFF” to „Manual/ON“:
1. Select control 2. Change operating state
After entering <1> in the group menu, the
following selection appears:
Q Quit
1 Auto
2 Manual
Select...:
Entering <2> activates „Manual“
The possible operating states for manual
control are now available:
Q Quit
1 OFF
2 ON
3 Heating
Select...:
Entering <2> activates „ON“
After making the desired entries, the operating dialog displays the result in the group
menu:
OpD 14:24:36 B P S – B E D I E N D I A L O G 12-APR-1998/MO
MENU * Group 3 AirCondOffice *
Q Back
1 Manual Control Actual status ON
Set status ON
The system technician installs menu-guided operation on commissioning, provided it
was requested on ordering. This includes:
– Installation of the software „New VISOTOOL Editor“ on the respective PC
– Loading the operating program „BPS Operating Dialog“ in the BPS
– Entering password protection „KEY1“ and „KEY2“ in the BPS
Menu-guided
operation
The main menu
Group menu functions
Example: Control and
operating state
Requirements