User Manual
Siemens Building Technologies CM2N8898E / 10.1999
Landis & Staefa Division 1/2
8
898
VISONIK
®
BPS operating hours count
Function sheet
This function sheet provides an overview of the VISONIK BPS operating hours
count functions.
The VISONIK BPS acquires the operating hours of plant elements through continuous
polling of the operating states. The VISONIK BPS can:
•
Add up operating hours and transfer them to the DCS
•
Determine limit value violations of operating hours
The illustration below shows an application example:
BPS
ML
P-Bus
8898Z01
SBR1
DCS
M02
M01
h
h
T
In this example, the VISONIK BPS acquires the following values:
Element Values
ML The duration of the frost status via the status module, point type ML
SBR1 The operating hours of the heating coil pump (M01) and the supply air fan
(M02) via feedback message of the switching modules, point type SBR1
The BPS transfers these values at intervals that can be defined to the Data and
Communication Server (DCS) for storage and further processing such as:
– Printing of spontaneous event reports
– Execution of maintenance reactions on reaching the operating hours limit values
Use
General
Example
Explanations (illustration)