User Manual
Siemens Building Technologies CM2N8878en / 01.05.02
Building Automation 1/4
8
878
VISONIK
®
BPS communication with BATIGYR
®
Function sheet
BATIGYR is a communicative individual room control system for fan coils.
Communication takes place via the BatiBUS. If a VISONIK system is used for
higher room management, the building process station (BPS) server as the
communication master.
The BATIGYR room temperature controllers and room units RCE86... control the
temperature of individual rooms and zones. The room temperature controllers
communicate with the VISONIK BPS (equipped with communication card COM1) via
the BatiBUS and the PNB interface. The BPS coordinates the individual devices and
integrates them in the higher management station.
BPS
8878Z01
DCS / Insight
RCE86...
PNB
BatiBUS
The BatiBUS is a global building field bus. It is promoted by the "BatiBUS Club Interna-
tional“ founded in 1989. The bus consists of a twisted 2-wire conductor. The
communications protocol is open and defined in different standards (NFC, CENELEC,
ISO/IEC).
In BATIGYR, the BPS has the following communication master tasks:
Tasks Examples
Providing information Operating mode, actual values, setpoints,
changeover.
Coordinating the RCE86... Grouping, master-slave relations.
BatiBUS supervision Communication between controllers and PNB.
Handling of electrical energy Controller outputs for the electrical heating coils.
Use
Topology
BatiBUS
Communication
master tasks