User Manual

CM2N8879en / 01.05.02 Siemens Building Technologies
2/2 Building Automation
The RCE individual room controllers and the SEZ switching units are grouped logically
in the BPS process image, and assigned to the @MGR and @MGG point types as
follows in accordance with the room distribution in the building:
MONOGYR rooms (@MGRn) featuring up to 10 controllers and 10 switching units.
MONOGYR groups (@MGGm) featuring up to 20 MONOGYR rooms @MGR.
@MGG1
.RCE5
.SEZ4
BPS
@MGR1
.RCE3
.RCE2
.RCE1
12 34 5
@MGR2
RCE RCE RCE RCESEZ
M-bus
8879Z02en
Group 1
Process image
Room 1
Room 2
Below is a list of the main functions of the MONOGYR rooms and groups:
Point type Functions
MONOGYR
room
@MGR
The point type @MGR helps to directly control one or several RCE
individual room controllers or SEZ switching units. Together with those
units, the following functions can be implemented:
Heating/cooling.
Heating/cooling with summer/winter changeover.
Heating/cooling in sequence (sequence control) with summer/winter
changeover for the second sequence (heating/cooling).
Adding the air speed as an auxiliary variable.
Switching a potential-free relay contact.
Acquiring the signaling contact.
MONOGYR
group
@MGG
Point type @MGG allows for carrying out the following higher tasks:
Automatic and manual assignment of the operating modes for the
MONOGYR rooms (Comfort, Economy, Reduced).
Default setting for corrected setpoints based on the outside
temperature.
Calculation of the air volume of MONOGYR rooms.
Statistical values on room occupancy, room temperatures (min.,
max., and median values), and controller outputs (min., max., and
median values).
Switch-on optimization OSC for heating and cooling:
Definition and registration of energy demand for MONOGYR rooms.
OnlythesamecontrollertypescanbeusedinaMONOGYRroomMGRn.
One master and up to nine slave controllers can be assigned to one MGRn.
No room units must be connected to the slave controllers.
The above functions can be operated via the BPS as the communications master.
Operation takes place via:
VISOTOOL Editor
VISONIK data and communication server DCS / VISONIK Insight.
POP cards (personal operating process cards).
For further information on this topic, refer to "VISONIK system basics", topic 13,
"MONOGYR in the BPS“.
Integration
Principle
Functions
Notes
Operation
Additional informatio
n
2002 Siemens Building Technologies Ltd.