User Manual

Siemens Building Technologies CM2N8881en / 02.2000
Landis & Staefa Division 1/2
8
881
VISONIK
®
Information points
Function sheet
In building automation and control, information points represent the data sources and
data sinks of the related process variables. Information points are identified by an
address and may contain one or several items of information. The term "information
point" in building automation and control is synonymous with "data point".
The illustration below shows an example for a VISONIK information point. All
information in the data point of type MW under the technical address $015 in the
process image of the BPS automation station is available for the basic function
MEASURING with temperature sensor T1:
MW
°C
BPS
etc. LOL
CPNR
DPD
16.5
0xxxx
AI
19.8
$015
.....
T1
- Address
- Parameter
- Values / information
Information point /
data point
8301Z39E
The smallest entity containing a statement on the process variable is considered one
item of information. In VISONIK data points, the individual items of information are
contained in the various parameters in the form of values. For the above example:
Parameter Information
DPD Present raw measured value of sensor T1
CPNR Conversion set no.; here: 0 for standard conversion to sensor Ni1000
AI Analogue Input = Present, converted measured value in °C; here: 19.8,
also main value for this information point.
LOL Assigned lower limit value; here: 16.5
Use
Example for an
information point
Information

Summary of content (2 pages)