If specified in the scope of delivery, engineering creates project-specific POP Cards
such as the "Timer" card for a heating group. This allows for accessing the functions of
the TSP timeswitch program.
The following picture shows the "Timer" card on the left and possible display values on
the right after inserting the card in the VISONIK BPS card compartment:
Time switch prog.
Input No.:
Start day
Stop day
Start
End
Oper. mode
Room temp. setpoint (day)
Room temp. setpoint (night)
Enable
Delete entry
1=Mo, 2=Tu, 3=We
4=Th, 5=Fr, 6=Sa
7=Su
11..17=SD1..SD7
0=Night
1=Day
1=yes
0=no
Time Switch Prog. Heating Group 1 Ad.11 Pg.1
Project Card
Display
Building Process Station
8891Z06E
1=Delete
The card allows for reading and changing the following values via the keys:
Value
Explanation
Entry no. Number of the respective entry in the timeswitch catalogue of this
plant. Each entry defines a timeswitch program.
Start day The start day of the entry in the form of a number; here: 1 for Monday.
Stop day The stop day of the respective entry; here: 5 for Friday.
Beginning
The beginning of occupancy for the respective heating group.
End The end of occupancy for the respective heating group.
Operating mode The operating mode for the selected days and occupancy times; here:
1=Day.
Setpoint day The room temperature setpoint assigned to operating mode "Day".
Setpoint night The room temperature setpoint assigned to operating mode "Night".
Activate Is the entry ready for processing? Here: 1 = yes.
Delete entry The displayed entry no., i.e., the respective timeswitch program can
be deleted by entering 1.
Note:
This card allows for using weekdays Mo…Su as well as special days SD1…SD7
as the start and stop days.
COLBAS commands (LIST, EDIT, DEL, etc.) that refer to destinations, timeswitch
catalogues and entries can also be used to create and change timeswitch catalogues.
This is done by means of a PC connected to the tool interface. Information on this
procedure is available in the documents listed below.
Refer to the following documents for more information on the VISONIK BPS timeswitch
program:
Document no. Title
CM2B8301E Building Process Station BPS, operating instructions
CM2T8567E VISONIK System Basics (expert documentation)
Example POP
Cards
The "Timer" card
Functions of the
"Timer" card
Timeswitch with
COLBAS
Further information on
the timeswitch program
1999 Siemens Building Technologies Ltd.