User Manual

Siemens Building Technologies CM2N8895en / 26.02.01
Landis & Staefa Division 1/4
8
8
95
VISONIK
®
BPS plant control
Function sheet
The VISONIK BPS plant control coordinates and implements all the control
functions of the building services systems assigned according to the plant
operating program created by engineering.
This document describes the elements and principle of operation of plant control.
Control functions in building services systems such as HVAC plants are carried out
chiefly as the result of certain events. The latter can be triggered by very varied
influences either inside or outside the plant. The following are some typical examples:
Influence Event
Þ
control function
Time 07:00 is reached:
Þ
Change ventilation from night to day operation.
Heating requirement Maximum heat output reached at Boiler 1:
Þ
Turn on Boiler 2.
Outside temperature Temperature falls below the frost protection limit:
Þ
Trigger the frost protection functions.
Degree of pollution The pressure difference between the two sides of the filter
is too high:
Þ
Output maintenance alarm “Replace filter mat”.
Operating hour Twin pump “A” reaches the operating hour limit:
Þ
Switch to twin pump “B”.
Plant elements Fan contactor is defective / No “ON” feedback message:
Þ
Switch off plant.
Energy requirement External heat surplus in the “south” plant part while there
is a heating demand in the “north” plant part:
Þ
Carry out energy-optimized demand switchovers.
Room occupancy Spontaneous evening event in the assembly hall:
Þ
Set the plant setpoint manually to day operation.
The VISONIK BPS implements the control functions using its basic and processing
functions, and according to the conditions for the participating elements set down by
engineering.
Use
Examples of control
functions
Implementation

Summary of content (4 pages)