User Manual

Siemens Building Technologies CM2N8899en / 01.05.02
Building Automation 3/4
The controllers integrated as data points can be operated via:
POP cards (standard cards / project cards).
PC with VISOTOOL Editor.
Insight station on the DCS.
FLN
RWI
DCS / Insight
TEC
TEC
TEC
VISOTOOL
Editor
POP cards
TEC rooms
TEC groups
RWI controllers
8899Z03en
RoomRoom
Group
Operation accesses the following data points and parameters (examples):
Data points Parameter for ...
TEC groups Default operating modes: Comfort, Economy, etc..
Setpoint defaults for heating/cooling in the operating modes.
Reading of calculated values. For instance, portion of Comfort (%),
median value of room temperatures, etc.
TEC rooms Default operating modes: Comfort, Economy, etc..
Associated setpoint defaults for heating/cooling.
Reading of current room temperature values.
Reading of current values for output signals to the actuating devices.
Link points Query point status, command output (blinds up/down, etc.).
RWI
controller
Operating mode defaults and setpoints for heating/cooling.
Reading of current values for inputs and outputs.
The room management report RMR (VISOTOOL Editor) displays or prints information
on groups, rooms, and controllers of the individual room control system on the screen
or printer. The following examples show the beginning of a room management report
for all TEC rooms TCR. The following are shown:
$d007’ TCR22, i.e., room TCR22 at BPS 007 with TEC controllers (T33..34).
RMR 08:23:54 REPORT-START 18-JAN-2001/TH
TCR $d007'TCR22 (T33..34)
18-JAN-2001 18:32:35 AOPST=Comfort RRTP=20.3 ERSTA=0
SOPST=Economy APRST=Fully occupied
SOMOD=Local ASTH =1 VSPA =0 m3/h
MACT =0 ASTC =0 VEXA =0 m3/h
MOPST=Economy RRSC =3 °C RWINO=Close
+-----+------+-----+-----+-----+-----+-----+-----+------+------+------+------+
! TEC ! ARTP !OHWA !OCWA !OXWA !OHAIR!OCAIR!OHHB !OEAIR ! OFAN !AIRVS1!AIRVE !
! ! !OHWA2!OCWA2!!!!! ! !AIRVS2! !
! ! [C] ! [%] ! [%] ! [%] ! [%] ! [%] ! [%] ! [%] ![m3/h]![m3/h]![m3/h]!
+-----+------+-----+-----+-----+-----+-----+-----+------+------+------+------+
! 33 ! 20.3 !0!0!0!0!35!0!35! 0! 0! 0!
!! !57!0!!!!! ! !0! !
+-----+------+-----+-----+-----+-----+-----+-----+------+------+------+------+
The report shows the values e.g. for the following parameters:
Present operating mode of the controller AOPST = Comfort.
Present room temperature ARTP = 20.3 °C.
For the other parameters, refer to the "BPS process image" document, volume 2.
Operation
Options
What can I operate?
RMR reports