BPS communication with TEC™
Function sheet
Terminal equipment controllers—short TEC—are communicative individual room
controllers. They can be linked to form a system via the floor level network (FLN).
If a VISONIK system is used for higher room management, the building process
station (BPS) server as the communication master (FLN master). AEROGYR
ventilation controllers RWI can be integrated in addition to TEC devices.
The TECs control and supervise the temperature or humidity of individual rooms. The
RWI controllers help control ventilation plants. Both device families can communicate
with the BPS via FLN (equipped with COM2 communication card). The BPS as the FLN
master coordinates the individual devices and integrates them in the higher
management station.
BPS
TEC
FLN
RWI
TEC TEC
DCS / Insight
8899Z01en
FLN master
The FLN master carries out the following tasks in addition to controlling and supervising
communication on the floor level network:
Task Examples
Provide information for users Operating mode, setpoints for heating and cooling,
present room temperature, etc..
Coordinate TECs Form TEC rooms and groups, calculate, transmit
operating values, etc..
Support RWI RWI data points, higher functions.
Allow for service action Enabling, valve purge, etc..
Use
Topology
Commissioning the
FLN master

Summary of content (4 pages)