User Manual

Connection diagrams for the SDLC ring
The connection diagrams below illustrate principal wiring of a VISONIK BPS on the
SDLC ring without field phone connection. More detailed instructions are provided in the
Mounting and Installation Handbook M8017E.
Connection of a
VISONIK BPS on the
SDLC ring
W1 Cable type 4-core twisted 4 x 1, star-4 III Terminal block III on the BPS
W2 Cable type twisted pair 2x 2 (communication card PVC1....)
1A IN A (SDLC ring) 11A IN A (SDLC ring)
2B IN B 12B IN B
3A OUT A 13A OUT A (amplified signals)
4B OUT B 14B OUT B (amplified signals)
7 Screened SDLC ring cable and earth
conductor *)
17 Screened SDLC ring cable and earth
conductor *)
*) The terminals 7 and 17 must be used only to earth the SDLC ring cable’s screening. Both connections are
internally connected via terminal block III. As a result, only one of them must be earthed. Connection G0 of
the BPS power supply is not connected to these terminals.
Wiring without ring signal amplification on
return: Only for short ring lines!
Wiring with ring signal amplification on
return.
Basic SDLC ring
wiring
6/6
Siemens Building Technologies Building Process Station CM2N8302en
Building Automation 28-Jan-04