User Manual
8
302
VISONIK®
Building Process Station
Overview
This data sheet provides the following information:
• Overview of unit types, connections, and accessories for the VISONIK building
process station(hereafter referred to as VISONIK BPS)
• Technical data on bus systems as well as wiring the BPS on the building level
network (SDLC ring)
• Engineering notes and overview of functions to generate application
programs.
Use
The VISONIK BPS is used in Commercial Buildings for sophisticated HVAC and related
tasks as follows:
Field of application
• As an independent unit within a building automation system or as a separate unit via
remote operation
• Together with other process stations on a building level network (BLN) with or without
a Master VISONIK station.
• As Master to integrate individual room controllers or standard process units via the
floor level network (FLN)
The building process stations can be used in VISONIK systems starting from version
V12 and they are downward compatible.
VISONIK system
family
Functions
The VISONIK BPS primarily serves to perform the following functions:
• Control and monitoring tasks (DDC applications).
• Exchange process-related data via:
− Process bus (P-bus) to the I/O modules
− Floor level network (FLN) to the terminal equipment controllers (TEC) as well as
the AEROGYR RWI ventilation controllers
− MONOGYR bus (M-bus) to MONOGYR units.
• Display process values at the BPS and executing issued commands in accordance
with the active POP card (Personal Operation Process Card)
• Communicate with directly connected peripheral devices for operation (PC, terminal)
or printing (printer)
• Data communication between partner stations on the building level network, Ethernet
(peer-to-peer) or via modem (remote operation)