User Manual
Siemens Building Technologies CM2N8877en / 01.05.02
Building Automation 3/4
The controllers integrated as data points can be operated via:
• PC with VISOTOOL Editor.
• Insight station on the DCS: Pictures created for each project.
• POP cards: Standard cards or cards created for each project.
DCS / Insight
VISOTOOL
Editor
LON
POP Cards
8877Z03en
Room
Room
HVAC group
Blinds
Light
Rooms
HVAC groups
Lighting/blinds groups
Operation as a rule accesses all data points integrated in the RX application. The exact
scope and operation depend on the project-specific implementation and the respective
operator unit. Examples:
Elements Operating scope (examples)
HVAC groups – Default operating modes: Comfort, Reduced, Economy, etc..
– Setpoint defaults for heating/cooling.
– Reading of calculated values. For instance, number of rooms with
Comfort or Economy operation, median value of room
temperatures, etc.
Rooms – Default operating modes: Comfort, Reduced, Economy, etc..
– Setpoint defaults for heating/cooling.
– Reading of current room temperature.
Blinds and
lighting groups
– State query for lighting and blinds groups.
– Command output: Blinds Up/Down, light On/Off.
The room management report RMR (VISOTOOL Editor) displays or prints information
on groups, rooms, and controllers of the individual room control system on the screen
or printer.
The following example shows the command the resulting report for room TCR74. The
report shows that this room contains one RX controller with TEC number 39. The report
shows its parameters and values:
rmr @tcr74
RMR 17:06:05 16-AUG-1999/MO
!FI TCR $d070'TCR74 (T39)
16-AUG-1999 17:04:18 AOPST=0
SOPST=0 APRST=0
SOMOD=0 ASTH =0 VSPA =0
MACT =0 ASTC =0 VEXA =0
MOPST=2 RRSC =0 RWINO=0
+-----+------+-----+-----+-----+-----+-----+-----+------+------+------+------+
! TEC ! ARTP !OHWA !OCWA !OXWA !OHAIR!OCAIR!OHHB !OEAIR ! OFAN !AIRVS1!AIRVE !
! ! !OHWA2!OCWA2!!!!! ! !AIRVS2! !
! ! [C] ! [%] ! [%] ! [%] ! [%] ! [%] ! [%] ! [%] ![Step]![m3/h]![m3/h]!
+-----+------+-----+-----+-----+-----+-----+-----+------+------+------+------+
! 39 ! 27.2 !0!100 !0!0!0!0! 0! 3! 0! 0!
!! !0!0!!!!! ! !0! !
+-----+------+-----+-----+-----+-----+-----+-----+------+------+------+------+
Examples: ARTP = Current room temperature.= 27.2 °C
OCWA = Positioning value at cooling output = 100 %
For the meaning of the other parameters, refer to the "BPS process image", volume 2.
Operation
Options
What can I operate?
Example for an RMR
report