User's Manual

Technical specifications
8.7 Switching frequency
M200D AS-Interface Basic
94 Manual, 03/2009, A5E01668085-01
3RK1315-5NS71-.AA. (1.5 A to 9 A)
Class 10
Device setup Vertical Horizontal
Rated current I
e
5 A 5 A 5 A 5 A 5 A 4.5 A
Ambient temperature 40 °C 50 °C 55 °C 40 °C 50 °C 55 °C
Degree of protection
1)
2)
1)
2)
1)
2)
1)
2)
1)
2)
1)
2)
ED=30 % (8xI
e
) / 0,5 s 120 700 120 520 120 420 120 580 120 430 120 430
ED=70 % (8xI
e
) / 0,5 s 70 400 70 280 70 200 70 340 70 200 70 200
ED=30 % (8xI
e
) / 1 s 60 350 60 260 60 220 60 290 60 220 60 220
ED=70 % (8xI
e
) / 1 s 37 190 37 140 37 100 37 170 37 100 37 100
1) Duty cycle current rms value = 1.15 x I
e
→ motor protection
2) Duty cycle limit for motor starter. The motor should be protected against overload here by means of a thermistor.
3RK1315-5NS71-.AA. (1.5 A to 9 A)
Class 10
Device setup Vertical Horizontal
Rated current I
e
7 A 5.8 A 5 A 6 A 5 A 4.5 A
Ambient temperature 40 °C 50 °C 55 °C 40 °C 50 °C 55 °C
Degree of protection
1) 2)
1) 2)
1) 2)
1) 2)
1) 2)
1) 2)
ED = 30 %, start 4xI
e
/2 s 120 290 120 300 120 320 120 320 120 320 120 320
ED = 70 %, start 4xI
e
/2 s 70 130 70 130 70 130 70 140 70 140 70 140
ED = 30 %, start 4xI
e
/4 s 60 145 60 150 60 160 60 160 60 160 60 160
ED = 70 %, start 4xI
e
/4 s 37 65 37 65 37 70 37 70 37 70 37 70
1) Duty cycle current rms value = 1.15 x I
e
→ motor protection
2) Duty cycle limit for motor starter. The motor should be protected against overload here by means of a thermistor.
3RK1315-5NS71-.AA. (1.5 A to 9 A)
Class 10
Device setup Vertical Horizontal
Rated current I
e
9 A 9 A 9 A 9 A 9 A 9 A
Ambient temperature 40 °C 50 °C 55 °C 40 °C 50 °C 55 °C
Degree of protection
1) 2)
1) 2)
1) 2)
1) 2)
1) 2)
1) 2)
ED = 30 %, start 4xI
e
/2 s 120 170 120 120 105 105 120 145 105 105 88 88
ED = 70 %, start 4xI
e
/2 s 70 140 70 100 70 80 70 120 70 82 63 63
ED = 30 %, start 4xI
e
/4 s 60 85 60 60 53 53 60 72 53 53 44 44
ED = 70 %, start 4xI
e
/4 s 38 72 38 50 38 38 38 60 38 41 31 31
1) Duty cycle current rms value = 1.15 x I
e
→ motor protection
2) Duty cycle limit for motor starter. The motor should be protected against overload here by means of a thermistor.