User's Manual

Diagnostics
7.2 Diagnostics with LED
M200D AS-Interface Basic
Manual, 03/2009, A5E01668085-01
83
SF LED STATE LED DEVICE LED Device faults
Red Red Red Current flowing with no ON command
(e.g.: contact welded, thyristor failure)
Red OFF Red Electronics defective, self-test fault
Red OFF OFF No connection with AS-i
System fault/alarm
SF LED STATE LED DEVICE LED System fault/alarm
Red OFF Yellow
Current not flowing despite ON command
(residual current detected)
Internal trip
Connector monitoring
Circuit breaker tripped / shut down
No contact block supply voltage
External encoder supply short-circuit
OFF Green
(when contact
block is ON)
Flashing yellow Group alarm due to:
Thermal motor model overload
Temperature sensor overload
Asymmetry
Incorrect parameter value
OFF OFF OFF No supply voltage for electronics
Group fault
SF LED STATE LED DEVICE LED Group fault
Red OFF OFF Device diagnosis available