User's Manual
Configuration / parameterization
5.2 Configuration on the AS-i master CP 343-2
M200D AS-Interface Basic
70 Manual, 03/2009, A5E01668085-01
5. Enter the following values for the AS-i profile:
NOTICE
ID1 code
The default setting of the ID1 code for M200D AS-i Basic is 7 (F).
A different setting is not permitted.
Field Value
IO code: 7 (B B B E)
ID code: A
ID1 code: 7 (F)
ID2 code: E
6. This completes the process of configuring the M200D AS-i Basic motor starter on the
CP 343-2 DP.