User's Manual
Installation / connection
4.2 Connection
M200D AS-Interface Basic
56 Manual, 03/2009, A5E01668085-01
Note the following rules when carrying out wiring:
Rules for flexible cables Data
Current-carrying capacity of the plug connection as a function of the
connectable core cross-sections and ambient temperature
T
U
=
55 °C
T
U
=
40 °C
1.5 mm
2
12 A 15 A
2.5 mm
2
20 A 25 A
4.0 mm
2
30 A 35 A
Unused connections
Seal unused connections by means of the sealing caps enclosed since this is the only way to
ensure degree of protection IP65.
The sealing caps are also available as accessories:
Item Quantity Order no.
Sealing cap M12 10 pieces 3RX9802-0AA00
4.2.2 Prefabricating power cables
To prefabricate power cables, you require the following:
● A crimping tool for attaching the sockets and pins on the individual wires
● For infeed on motor starters
Assignment of X1: see section Power terminal (Page 58):
– A flexible Cu
cable with 4 x 2.5 mm
2
/ 4 mm
2
/ 6 mm
2
(3 wire + PE)
(for motor starters with 230 V AC brake output: 5-core cable; 3 wire + N + PE)
– Han Q4/2 socket power connector
Item Quantit
y
Order no.
Contact socket 2.5 mm
2
, for Han Q4/2 sockets 5 3RK1911-2BE50
Contact socket 4 mm
2
, for Han Q4/2 sockets 5 3RK1911-2BE10
Contact socket 6 mm
2
, for Han Q4/2 sockets 5 3RK1911-2BE30
Crimping tool ≤ 4 mm² 1 3RK1902-0CT00
Crimping tool 4 / 6 mm² 1 3RK1902-0CW00