User's Manual

Functions
3.9 Communication
M200D AS-Interface Basic
40 Manual, 03/2009, A5E01668085-01
If no motor ON command is present, a group alarm is output.
The alarm is canceled when motor protection is reactivated.
If a motor ON command is present, a group fault is output immediately and a
corresponding internal shutdown command generated, which must be acknowledged with
"trip reset".
If the motor ON command remains, the fault can only be acknowledged with "trip
reset" once the fault has been rectified (activate at least one motor protection
function).
If the motor ON command is reset, the group fault can be "downgraded" to a group
alarm even if a setting is incorrect.
3.9.3 Message output
Message Meaning Output via
General messages
Ready (automatic)
Device can be controlled via BUS
Automatic mode
No fault
Process image of inputs
Group fault At least one fault is set.
LED
Diagnostics via parameter
channel
Group alarm At least one alarm is present.
LED
Diagnostics via parameter
channel
Mode monitoring
Manual operation
local mode
Manual operation via integrated
manual local control or via the local
device interface (hand-held device)
Diagnostics via parameter channel