User's Manual
Functions
3.9 Communication
M200D AS-Interface Basic
40 Manual, 03/2009, A5E01668085-01
● If no motor ON command is present, a group alarm is output.
The alarm is canceled when motor protection is reactivated.
● If a motor ON command is present, a group fault is output immediately and a
corresponding internal shutdown command generated, which must be acknowledged with
"trip reset".
– If the motor ON command remains, the fault can only be acknowledged with "trip
reset" once the fault has been rectified (activate at least one motor protection
function).
– If the motor ON command is reset, the group fault can be "downgraded" to a group
alarm even if a setting is incorrect.
3.9.3 Message output
Message Meaning Output via
General messages
Ready (automatic)
• Device can be controlled via BUS
• Automatic mode
• No fault
Process image of inputs
Group fault At least one fault is set.
• LED
• Diagnostics via parameter
channel
Group alarm At least one alarm is present.
• LED
• Diagnostics via parameter
channel
Mode monitoring
Manual operation
local mode
Manual operation via integrated
manual local control or via the local
device interface (hand-held device)
Diagnostics via parameter channel