User's Manual

Functions
3.9 Communication
M200D AS-Interface Basic
Manual, 03/2009, A5E01668085-01
39
3.9.1 Mode monitoring
Data channels
The M200D AS-i Basic motor starter has three different data channels:
Local optical device interface (for hand-held device)
Control with integrated manual local control in "Manual operation local" mode
(key-operated switch + keypad; order variant)
Via the fieldbus interface AS-Interface:
Cyclic data via AS-i
The data channel used for control purposes depends on the operating mode.
Operating modes
The following operating modes are available (in ascending order of priority):
Automatic (lowest priority)
The motor starter can only be controlled with the PLC via the fieldbus.
Manual operation local
The motor starter can be controlled with:
Integrated manual local control (key-operated switch + keypad; order variant)
Local device interface (e.g. hand-held device) (highest priority)
In this operating mode, the message "Manual local operation" is output when diagnosis is
performed via the parameter channel.
3.9.2 Plausibility check for settings
Description
The motor starter checks all the parameters that have been set to ensure that they are valid
and plausible.
Motor protection deactivation rule
At least one of the motor protection functions supported by the motor starter (thermal motor
model, temperature sensor) must always be active at any one time, that is, you are not
permitted to deactivate all the motor protection functions by means of parameterization.
If the temperature sensor is deactivated via the DIP switch and, at the same time, the rotary
coding switch is set to "Class OFF", the following applies: