6. Dispose of old battery through an approved battery re-cycling centre.
7. Connect new battery ensuring the latching clip is engaged.
8. Place battery in correct orientation into the enclosure.
9. Replace battery cover and tighten nuts.
10. Reconnect the supply, enable the battery with the battery isolation switch.
7.3.5 Replacing Fuses
The system contains two fuses that are located on the PSU board. To replace either of
these follow this procedure:
When replacing a fuse it is important to fit the correct type and rating for
continued protection of the Stratos Outstation and users equipment.
Before changing any fuses ensure that the unit is disconnected from the AC mains supply
and that the battery is isolated using the front panel switch S1.
PSU Board Fuse:
Figure 21 – Power Supply Board