7 MAINTENANCE 
Before attempting any maintenance work the following must be performed: 
1. Ensure the unit is powered off and isolated from the mains. 
2. Ensure the battery isolation switch on the front panel is switched to ‘OFF’. 
3. Remove all connectors that interface with external equipment (as some of these 
may have mains potential voltages present on them). 
If multiple I/O boards are fitted make a note of the board address against 
the plugged in loom before removing along with the position of each 
connector (top & bottom position). 
4. Remove the unit from its mounted position. 
7.2 Regular Maintenance 
Units only require annual maintenance, which can be performed at the same time as the 
inspection of other equipment on site. On these visits, trained personnel must switch off 
the mains power to the controller and the unit. 
Regular Maintenance Activity  Frequency
General inspections of the unit in situ for any contamination, overheating 
of components, corrosion or battery leakage. Rectify where necessary. 
Annual 
Check the tightness of all interface and earth cables and re-tighten where 
necessary. 
Annual 
Check the condition of the interface cables; making sure there is no 
chafing of the insulation and that the general condition of the insulation is 
good. Replace any damaged or worn cables. 
Annual 
Check the mechanical tightness of the main securing screws of the unit 
and retighten where necessary. 
Annual 
Replace battery as indicated by the battery test which is automatically 
performed approximately every 30 days. 
As required 
7.3  First Line 
Replacement of the following components is considered first line maintenance. 
Maintenance work beyond the first line should be referred to Siemens. Part numbers and 
spares are listed in the Appendix. 
Authorised agents may replace the following: 
  CPU Card (section 7.3.1) 
  IO Card (section 7.3.3) 
  Battery (section 7.3.4) 
  Fuses (section 7.3.5) 
  Cables and wiring 