Installation guide
Mobility and Logistics, Traffic Solutions
Sopers Lane, Poole, Dorset, BH17 7ER
Security classification Unrestricted Page 37 of 84
Version 1 Status Issued
Last Editor Carl Rabe Date 11-Dec-2014
Document Name Stratos Outstation General and ICM Handbook Document No. 667/HB/52250/000
Copyright © Siemens plc 2014. All Rights Reserved. Mobility and Logistics is a division of Siemens Plc
Note *
1
Providing none of the following conditions are true:
Ambient temperature extreme (outside of battery charging range which is -20°C
to +60°C).
Battery providing backup power.
Battery high voltage fault.
Battery charger forced off by user.
Under these conditions the battery self tests are inhibited and do not run.
Note *
2
- The test is delayed if the temperature is outside the battery range or if there has
been a mains failure in the previous 12 hours.
Note *
3
- It is not possible to precisely specify the point at which the battery is deemed
faulty and should be replaced. The battery capacity and on-load test results allow the user
to determine what constitutes a faulty battery. The user can extract the previous battery
capacity and on-load test results from the system log. This data can be used to help
understand how quickly the battery capacity has taken to decline, and determine when the
battery will need to be changed. A battery capacity test pass indicates the battery capacity
is greater than 25%, however, the test is indicative only as the actual support time
required will depend on the equipment connected.